BACnet MS/TP
X2 - Technical Documentation for BACnet MS/TP communication
Features
- BACnet MS/TP communication over RS485
- B-ASC Device Profile
- Supports up to 5 Change Of Value (COV) subscriptions
- Slave type of communication
- Supports up to 128 nodes on one network
- Galvanic isolated bus connection
- Baud rates: Auto / 9600 / 19200 / 38400 / 57600 / 76800 / 115200
- LED indicators
X2-BAC Protocol Implementation Conformance Statement (PICS)
Vendor Name: Vector Controls
Product Name: X2 Controls series
X2 product description:
The X2 communicating BACnet controllers are designed as universal controls equipment suitable for a large number of applications. They may be used in zoning and other applications which are monitored by a BACnet MS/TP network.
Supported BACnet® Interoperability Blocks (BIBB)
The BACnet® interface conforms to the B-ASC device profile (BACnet® Application Specific Controller).
The following BACnet® Interoperability Building Blocks (BIBB) are supported.
BIBB |
Type |
Name |
DS-RP-B |
Data sharing |
Read property - B |
DS-RPM-B |
Data sharing |
Read property multiple - B |
DS-WP-B |
Data sharing |
Write property - B |
DS-COV-B |
Data sharing |
Change of value - B |
DM-DCC-B |
Device management |
Device communication Control - B |
DM-DDB-B |
Device management |
Dynamic device binding - B |
DM-DOB-B |
Device management |
Dynamic object binding - B |
DM-TS-B |
Device management |
Time synchronization - B |
DM-UTC-B |
Device management |
UTC Time synchronization - B |
DM-RD-B |
Device management |
Reinitialize device - B |
Supported standard BACnet® application services
- ReadProperty
- ReadPropertyMultiple
- WriteProperty
- ChangeOfValue (max. 5 COV subscriptions supported)
- DeviceCommunication. Needs a password which is “Vector” (case sensitive and without the quotes).
- I-Am
- I-Have
- TimeSynchronisation
- UTCTimeSynchronisation
- ReinitializeDevice (“cold” or “warm”). Needs a password which is “Vector” (case sensitive and without the quotes).
Supported standard Object types
- Device
- Analog input
- Analog value
- Binary value
- Multi-state Value
- Network Port
Documentation
Engineering Manual:
Application Note:
Certificate
BTL:
Archive
Old Engineering Manual:
Old Application Note: