SCC-T1-Tpx - PT100/PT1000
Programmable temperature transmitter for PT100 and PT1000 probes for a wide and accurate measurement range
The transmitter measures the temperature through a PT100 or PT1000 platinum film element.
SCC-T1-TP1 measures a PT100 element, SCC-T1-TP2 measures a PT1000 sensing element. The temperature range may be customized by DIP switches or by programming.
The output signal range and type may be customized by jumpers or by programming. Standard output signal ranges are 0-10VDC, 2-10VDC, 0-20mA and 4-20mA. Other ranges can be set on the optional built-in operation terminal “OPC-S V2” or by connecting an external operation terminal “OPA-S / OPU-S”.
For more details, see the operation manual in the downloads section.
Applications
- For indoor, outdoor, duct, immersion temperature measurement in the field of heating, ventilation and air conditioning applications
- Measure exactly the temperature range you need
- Recording of minimum and maximum values for critical environments
- Supervision of critical temperatures
Type Overview (see ordering / accessories for details)
Standard SCC | SCC with duct probe | SCC with built-in operation terminal |
|
SCC-T1-Tp2-08/-16/-24 |
OPC-S-V2 |
Features
- Precision temperature measurement for different ranges and accuracies
- Minimum and maximum temperature memory
- 0…10V, 0…20mA or 2…10V, 4…20mA measuring signal output, selectable with jumpers
- DIP switch for temperature range pre-set
- Alternative temperature signal ranges programmable (operation terminal)
- Selectable averaging filter for the measurement signal
- Optional LCD display (OPC-S V2) or external display (OPA-S / OPU-S)
- Status LED
- Modbus RTU/ASCII RS485 for monitoring and configuration
- Copy of settings with accessory (AEC-PM2)
Selectable Temperature range by DIP switch
SCC-T1-TP1 | SCC-T1-TP2 | |||
DIP | [°C] | [°F] | [°C] | [°F] |
0 | -40…60 °C | -40…140 °F | -40...400 °C | -40...752 °F |
1 | 0…50 °C | 32…122 °F | -40…60 °C | -40…140 °F |
2 | 0…100 °C | 32…212 °F | 0…50 °C | 32…122 °F |
3 | 0…200 °C | 32…392 °F | 0…100 °C | 32…212 °F |
4 | -60…200 °C | -76…392 °F | 0…250 °C | 32…482 °F |
5 | -40…150 °C | -40…302 °F | -40…150 °C | -40…302 °F |
6 | -20…80 °C | -4…176 °F | -20…80 °C | -4…176 °F |
7 | -15…35 °C | 5…95 °F | -15…35 °C | 5…95 °F |
Ordering
Product name | Product No. | Description |
SCC-T1-Tp1-1 | 40-300258 | Temperature transmitter for PT100 sensor (sensor not included) with 2 cable glands |
SCC-T1-Tp2-1 | 40-300157 | Temperature transmitter for PT1000 sensor (sensor not included) with 2 cable glands |
SCC-T1-Tp2-08-1 | 40-300159 | Temperature transmitter with PT1000 duct sensor probe, length 8 cm |
SCC-T1-Tp2-16-1 | 40-300111 | Temperature transmitter with PT1000 duct sensor probe, length 16 cm |
SCC-T1-Tp2-24-1 | 40-300112 | Temperature transmitter with PT1000 duct sensor probe, length 24 cm |
SCC-T1-Tp2-MOD-1 | 40-300241 | Temperature transmitter, for PT1000 sensor (sensor not included) with 2 cable glands and Modbus communication |
SCC-T1-Tp2-08-MOD-1 | 40-300242 | Temperature transmitter, with PT1000 duct sensor probe, length 8 cm and Modbus communication |
SCC-T1-Tp2-16-MOD-1 | 40-300243 | Temperature transmitter, with PT1000 duct sensor probe, length 16 cm and Modbus communication |
SCC-T1-Tp2-24-MOD-1 | 40-300244 | Temperature transmitter, with PT1000 duct sensor probe, length 24 cm and Modbus communication |
Dimensions
Dimensions mm (inch)
SCC-T1-Tp1-1 or SCC-T1-Tp2-1
SCC-T1-Tp2-08/-16/-24 (SCC with duct probe)
Connections
Connections
SCC-T1-Tp2-1
SCC-T1-Tp2-08/-16/-24 (SCC with duct probe)
Accessories
Downloads
Operation Manual
Install Sheet
- 70-00-1005A SCC-T1-Tp2 install.pdf
- 70-00-1006A SCC-T1-Tp2 duct install.pdf
- 70-00-1040A SCC-T1-Tp1 install.pdf
Application Notes
Certificates
Archive